Y301-220/222 Technical Manual
This manual details the installation, wiring, and Modbus configuration steps for the dual-channel Y301-220/222 relay I/O modules. Y301-220 offers 2× DI and 2× SPDT DO. Y301-222 adds 2× analog inputs (AI) with selectable ranges per channel.
Table of Contents
- Introduction
- System Overview
- Hardware Interfaces
- Electrical Specifications
- Modbus Communication Parameters
- Configuration Workflow
- Automation & Linkage Rules
- Wiring Guidelines
- Diagnostics & Maintenance
1. Introduction
- Communication: Modbus-RTU slave over RS485 (default) or RS232.
- Power input: 5–36 VDC, reverse-polarity protected.
- Operating range: -40 °C to +85 °C, 35 mm DIN rail or screw mounting.
- Channels: 2× opto-isolated DI, 2× SPDT relay DO for both models; Y301-222 adds 2× AI.
- Addressing: Software slave address (1–255) plus optional DIP offset (0–31) on supported revisions.
2. System Overview
- DI support dry/wet contacts with 5–255 ms debounce and 32-bit pulse counting.
- DO are SPDT relays (AC 277 V / 10 A, DC 28 V / 10 A) with optional soft/power retention.
- AI (Y301-222) accept per-channel 0–10 V, 0–5 V, or 4–20 mA with 16-bit resolution.
- LED indicators show power, heartbeat, DI states, DO states, and serial TX/RX activity.
- Reload push button (if equipped) restores defaults after a 3–15 s hold.
3. Hardware Interfaces
- Power: V+/V− screw pair plus 5.5 × 2.1 mm DC jack.
- DI block: COM+, COM−, DI1–DI2 (dry loop via COM+; wet input 5–36 V referenced to COM−).
- DO block: NO/COM/NC per relay (DO1, DO2).
- AI block (Y301-222): AI− plus V+/I+ per channel, voltage and current inputs mutually exclusive.
- Communication: RS485 A/B/GND or RS232 TX/RX/GND share the same 3-position terminal.
- DIP switch: 5-bit Modbus address offset (ON = 1) on models that include the switch.
4. Electrical Specifications
- Supply: 5–36 VDC, typical draw 120 mA @12 V, max 180 mA with relays engaged.
- Digital Inputs: 2 channels, <5 mA each, 100 Hz sampling, 5–36 V wet threshold.
- Digital Outputs: 2 SPDT relays, AC 277 V / 10 A or DC 28 V / 10 A, <10 ms pickup, <5 ms release, 100 k cycles.
- Analog Inputs (Y301-222): 2 channels, 0–10 V / 0–5 V / 4–20 mA, ±1% FS accuracy, 16-bit resolution, 10 Hz sampling per channel.
5. Modbus Communication Parameters
- Addressing: Holding register 40063 (1–255). DIP offset adds 0–31 for quick staging.
- Baud Rate: 600–230400 bps (default 9600) via register 40088.
- Frame: Standard Modbus-RTU with CRC16.
- Supported Function Codes: 0x01, 0x02, 0x03, 0x04 (Y301-222 AI), 0x05, 0x06, 0x0F, 0x10.
- Automation Registers: Begin at PLC 40129 (0x0080); each rule uses 16 bytes.
- Pulse Counters: PLC 41281 and 41283 map to DI1/DI2 counts (write zero to clear).
- Special Register: 0x0800 write 0x5500 to reboot, 0x0055 to restore defaults.
6. Configuration Workflow
- Connect via HYToolBox, Modbus Poll, or any RTU master.
- Discover devices with broadcast address 0 if required; set unique base address (40063).
- Adjust baud/parity/stop bits using registers 40088–40092 to match network settings.
- Configure debounce (40067) and pulse edge (40066) to fit DI signal behavior.
- Select DO retention mode (40065) when relay states must survive reset.
- Program automation rules as 16-byte blocks from register 0x0080 upward (two rules per DO).
- Store device name, heartbeat payload, and broadcast mode if SCADA identification is needed.
7. Automation & Linkage Rules
- Mode list matches firmware table: DI Follow, Reverse, Pulse, Delay On/Off, Cycle, Timer, Daily schedule, AI threshold (Y301-222), Button, Watchdog, Logic.
- Two rules per DO (total four). Evaluate rules in ascending register order to avoid conflicts.
8. Wiring Guidelines
- Power: 22–18 AWG with upstream 1–2 A fuse; keep runs short.
- DI: Dry = COM+ through switch to DI. Wet = external 5–36 V to DI with COM− return.
- DO: Add snubbers (AC) or flyback diodes (DC) on inductive loads; respect relay ratings.
- AI (Y301-222): Voltage mode uses V+ to field signal and AI− return. Current mode wires loop source → I+ → AI−; keep only one mode active per channel.
- RS485: Shielded twisted pair with 120 Ω termination at both ends; share reference ground across nodes.
9. Diagnostics & Maintenance
- LED meanings: POWER steady = supply OK; WORK blink = heartbeat; DI/DO LEDs mirror channel states; TX/RX blink with traffic.
- Reload button resets configuration while preserving DIP offset.
- Semiannual checks: tighten terminals, inspect insulation, verify Modbus error counters.